Perle Systems IOLAN SCS Manual do Utilizador Página 160

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 159
Serial Port Profiles
160 IOLAN SDS/SCS/STS User’s Guide, Version 3.6
Trigger When the trigger condition is met, triggers the specified alarm action.
Data Options:
z Disabled—No alarm settings. This is the default.
z Inactive—When the expected Digital input is active, going inactive will
trigger an alarm.
z Active—When the expected Digital input is inactive, going active will
trigger an alarm.
Default: Disabled
Auto Clear Mode When enabled, automatically clears the alarm when the trigger condition
changes; for example, if the
Trigger is Inactive and the alarm is triggered, once
the input becomes active again, the alarm will automatically be cleared
Default: Enabled
Manual Clear
Mode
When enabled, a triggered alarm must be manually cleared.
Default: Disabled
Email When enabled, sends an email alert to an email account(s) set up in the System
settings when an alarm is triggered or cleared. The email alert data includes the
severity level and the value that caused the alarm to trigger or clear. The
Email
Alert is associated with Level Critical.
Default: Disabled
Syslog When enabled, sends a message to syslog when an alarm is triggered or
cleared. The syslog entry includes the severity level and the value that caused
the alarm to trigger or clear. The syslog message is associated with
Level
Critical.
Default: Disabled
SNMP When enabled, sends an SNMP trap when an alarm is triggered or cleared. The
trap consists of the severity level and whether the alarm was triggered or
cleared.
Default: Disabled
Vista de página 159